Product Features
Application Range
GDSC100R series PV Switch-disconnector is suitable for rated voltage DC1200V and below, rated current 32A and below power system. The product can be used for infrequent connection and disconnection, which can isolate the disconnection line and disconnect 1~4 MPPT lines at the same time. It is suitable for isolating lines in DC transmission and distribution systems, such as cutting the direct current circuit between solar panels and inverters.
Features
- IEC/EN 60947-3andAS 60947.3
- Utilization category: DC-PV1,DC-PV2
- Non polarity
- IngressProtection:DS1-32(IP20),DS1-32EL(IP66)
- OFF Lockable
- UV resistant and Flammability UL94 V-0
- Arcing time <2ms
Dimensions
Parameter
Data | ||
Electrical characteristic | ||
Model number | GDSC100R-DB32R/GDSC100R-EL32R | |
Feature | Isolation and control | |
Standard | IEC60947-3, AS60947.3 | |
Utilization category | DC-PV1/DC-PV2 | |
Pole | 4P | |
Rated frequency | DC | |
Rated operating voltage (Ue) | 300V/600V/800V/1000V/1200V | |
Rated insulation voltage (Ui) | 1200V | |
Rated short-time withstand current (Icw) | 1kA/1s(4,4S,4B), 1.7kA/1s(2H) | |
Rated conditional short-circuit current (Icn) | 3kA | |
Rated impulse withstand voltage (Uimp) | 8.0kV | |
Overvoltage category | II | |
Polarity | No polarity, “+” and “-” polarities could be interchanged | |
Service Life/Cycle Operations | ||
Mechanical | 15000 | |
Electrical | 300 | |
Installation environment | ||
Ingress protection | IP20 | |
Storage temperature | -40°C~+85°C | |
Mounting type | Vertically or horizontally | |
Pollution degree | 3 |
User Manual
Products Categories
Get A Free Quote