The GYM10H DC circuit breaker is designed for DC circuits with rated voltage up to 1000V and rated current up to 63A, providing overload and short-circuit protection, and can also be used for infrequent circuit switching operations.
This breaker is suitable for DC system applications such as telecommunications and photovoltaic (PV) systems.
Compliant with standards: IEC/EN 60947-2, GB/T 14048.2.
Contact Position Indication Function.
Maximum Wiring Capacity 16mm2.
Dual busbar and no busbar options available.
Technical Specification
- Rated Current(In): 6、10、16、20、25、32、40、50、63A
- Rated Voltage(Ue): 1P:250VDC; 2P:500VDC; 3P:750VDC; 4P:1000VDC
- Rated insulation voltage: 500V
- Rated impulse withstand voltage (Uimp): 4kV
- Tripping Curves: B:(6±20%)In、C:(8.5±20%)In、D:(12±20%)In
- Breaking Capacity: 4.5kA
- Poles: 1P、2P、3P、4P
- Mechanical life: 20000 times
- Electrical life: 10000 times
- Tightening moment: 2.0N.m
- Class of protection: Ip20
Wiring Diagram
Outline Overall And Installing Dimensions
Temperature Compensation
When the ambient temperature is not the baseline temperature of 30℃, the reference Correction coefficientis as follows:
Ambient Temperature | -20°C | -10°C | 0°C | 10°C | 20°C | 30°C | 40°C | 50°C | 60°C |
Current Correction Factor | 1.25 | 1.2 | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |